Electrical supply

Electrical power is provided to the building by UKPN at 11kV

The incoming UKPN HV switchgear is in the lower ground floor area
Metering is provided by UKPN at their incoming room at 11kV level

Design criteria

Lighting: 7W sq m

Small power: 25W sq m

Supplementary small power: 10W sq m

A Landlord’s generator will provide full life safety backup.

Provision has been made at roof level for a tenant standby generator(s)
with a tenant oil storage plantroom available at basement level